Figure 2.21
TM 5-6630-218-10
2.5.1.1 Method for Undissolved Water Testing
Undissolved water in the fuel sample will react with the free-water pad dye
for detection and measurement with the Aqua-Glo® Water Detector.
Collect a 500 milliliter (17.0 ounce) sample of fuel. Pass the fuel sample
through the sampler with the free-water test pad contained within the stainless
steel monitor. Remove the free-water test pad from the monitor and blot dry
between paper towels. Insert the free-water test pad into the Aqua-Glo Water
Dectector and read and record ppm of water.
All parts and tools referred to in the following steps can be identified in
Figure 1.1, page 1-5, or on the test kit placard (see Loading Plan).
2.5.1.2 Calibrating the Aqua-Glo Water Detector